Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
3P 4P 200A - 6300A Intelligent Air Circuit Breaker Fixed Type Or Draw Out Type GTW1
Technical specifications
Frame size rated current Inm (A) | Rated current In A |
2000 | 400,630,800,1000,1250,1600,2000 |
3200 | 2000,2500,2900,3200 |
4000 | 3200,3600,4000 |
6300 | 4000,5000,6300 |
Circuit breaker rated short-circuit breaking capacity and rated short-time withstand current, Arcing- over distance is zero.
Size current Inm (A) | 2000 | 3200 | 4000 | 6300 | |
Rated limit short-circuit breaking | 400V | 85 | 100 | 100 | 120 |
690V | 50 | 65 | 65 | 80 | |
Rated short-circuit connecting capacity N×Icu (KA)/ cos | 400V | 176/0.2 | 220/0.2 | 220/0.2 | 264/0.2 |
690V | 105/0.25 | 143/0.2 | 143/0.2 | 187/0.2 | |
Rated operating short-circuit breaking | 400V | 50 | 65 | 65 | 80 |
690V | 40 | 50 | 50 | 70 | |
Rated operating short-circuit breaking | 400V | 50 | 65 | 65/80(MCR) | 85/100(MCR) |
690V | 40 | 50 | 50/65(MCR) | 65/75(MCR) | |
Note: last hour line and next enter line of breaking capacity in the table are the same. |
Earthing fault
Largest power loss of the breaker is 360W. Breaker’s rated continuous current changes under different conditions.
TemperatureGTW1 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Note: 2500A or above derating factor is 0.9, including 4000A none-derating among 6300A. |
Intelligent over-current controller protection characteristic and function
Over-current controller protection feature
a.Controller’s setting value Ir (I/ In) and accuracy
Long-delay | Short-delay | Instantaneous | arthingfault | ||||
Ir1 | Ir2 | Accuracy |
| Ir3 | Accuracy | Accuracy | |
(0.4-1)In | (0.4-15)In | ±10% | In~50KA(Inm=200A) | ±15% | Inm=2000~4000A(0.2~0.8) | Inm=6300A(0.2-1.0)In | ±10% |
Note:when required three-section protection at the same time,setting values can’t intercross. |
b.Long time delay overcurrent protection characteristics I2TL=(1.5Ir1) 2 tL Operative time of (1.05~2.0)Ir1 view table below, time accuracy
is ±15%.
Note: tL- long time delay setting for 1.5 Irs, TL- long time delay operative time
c.Short time delay over-current protection characteristic
d.Short time delay over-current protection is with fixed time setting. When inverse time limit is required to be low multiples, its characteristic
should according to I2Ts=(8Ir1) 2 ts, ts is for common delay time setting; when pver load current >8 Ir1 , automatically changes to fixed
time setting characteristic, its characteristic view table below, time accuracy is ±15%.
Delay time(s) | Returnable time(s) | |||||
0.3 | 0.4 | 0.06 | 0.14 | 0.23 | 0.35 |
d.over-current protection characteristic view graph1,earthing fault protection characteristic view graph2.
Description:
GTW1 Series air circuit breaker is applicable for distribution network of AC 50HZ, rated voltage of 400V and 690V, and rated current of 630A~6300A, to distribute electric energy protection circuit and prevent power equipments from harm of overload, under-voltage, short circuit and single phase earth etc. Provided with intelligent protecting function and precise selective protection, breaker can enhance the dependability of power supply and avoid unwanted power cut.
Competitive Advantage:
<> ISO9001 quality management system
<> ISO14001 environmental management system
<> Three OHSAS18001 Occupational Safety and Health Management System certification
<> PCCC certification and energy-saving products certification for compulsory product certification
<> GB1094.1-1996 GB1094.2-1996 JB/T 10088-2004
<> GB1094.3-2003 GB1094.5-2008
<> GB/T 6451-2008 GB/T 7595-2008 JB/T 3837-2010
<> 6S Management System
<> "National User Satisfying Enterprise"
<> "National Second-level Safety Standardization Enterprise"
<> "The Most Growing Private Enterprise of China"
<> "Zhejiang Standard Innovation Type Enterprise"
<> "Zhejiang Business Enterprise Credit AAA Level Unit Loyally Abiding by Contracts and Credits"
<> "Chinese Famous Brand", "Zhejiang Famous Brand" and " Wenzhou Famous Brand Products"
<> "Zhejiang Well-known Firms"
<> "National Torch Plan Project"
<> "National Spark Program Projects"
<> "Zhejiang Major Science and Technology Special"
<> "Zhejiang Science and Technology Award"
WHY CHOOSE US? ADVANTAGES
1. Direct manufacturer, high quality guaranteed.
2. No cheating on workmanship and materials.
3. Large investment in R&D, keep upgrading products.
4. Specifications are real and reliable, with highly recommended certificates.
5. Complete product range, provide compact power solution.
6. Advanced assembly line equipment with professional workers.
7. All types of transformers, frame breaker and circuit breakers with mature technology.
Applications:
Frame circuit breaker is the protection of low voltage electrical equipment. The main purpose is to avoid over current, under voltage, short circuit, and so on and so prevent the damage. General application is in the location of the transformer or the front line. Such as the total control circuit of the whole building or transformer room.
How To Contact Me?
Email: nicholas.shen@jubanghk.com
Phone: +86 755 28069300
Fax: +86 755 29813657
Skype: Nicholas201310
WhatsApp: +86 18681480860
Jubang Electric Group Co., Ltd. [China (Mainland)]
Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)