Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
10kv 13kv 650A 100A HV Switch Vacuum Circuit Breaker With Fuse
What are the specifications of our FK(R)N12A-12D series indoor HV cacuum circuit breaker?
1. Description:
FK(R)N12A-12D/T630-20 type indoor AC HV load switch is an indoor three-phase 50Hz 12KV device. It is used for controlling on and off load current, closed-loop current,no-load transformer, cable charging current and on and off short-circuit current. The earthing switch can support short-circuit current.
FK(R)N12D/100-31.5 type AC HV load switch and fuse combination apparatus (short for FN12-12D.R combination apparatus) is a indoor HV apparatus,it is consists of FN12-12D load switch and S_LAJ-12(XRNT_-12) HV current-limiting fuse. It can break any kind of opposite current caused by short-circuit reliably, such as load switch breaking operating current, fuse breaking short-circuit current, joint breaking operating current and dead-short-circuit current.
2. Product data:
Main technical specification
No. | Item | Unit | FKN12-12D/630-20 | FKN12-12D.R/100-31.5 |
1 | Rated voltage | KV | 12 | |
2 |
Rated frequency |
Hz | 50 | |
3 | Rated current | A | 630 | 100 |
4 | Lighting impulse withstand voltage | kV | Earthing and inter-phase 75, insulating fracture 85 | |
5 | I min power frequency withstand voltage | kV | Earthing and inter-phase 75, insulating fracture 48 | |
6 | Rated short-time withstand current | KA | 20(4s) | |
7 | Rated peak value withstand current | KA | 50 | |
8 | Rated short-circuit closing current (peak) | KA | 50 | |
9 | Rated short-circuit breaking current | KA | 31.5 | |
10 | Rated transfer current | KA | 1.5 | |
11 | Rated breaking no-load transformer capacity | kVA | 1250 | |
12 | Rated current of charge cable | A | 10 | |
13 | Rated active load current breaking times | Times | >1000 | |
14 | Impactor trigger load switch breaking time | s | >0.06 | |
15 | Earthing switch rated short-time withstand current |
kA | 20(2s) | |
16 | Earthing switch rated peak value withstand current |
kA | 50 | |
17 | Power voltage of motor operating | V | AC220,DC220 |
Machine feature
No. | Item | Unit | FKN12-12D/630-20 | FKN12-12D.R/100-31.5 |
1 | Moving contact travel distance | mm | 218+8-2 | |
2 |
Static contact travel distance |
mm | 58±2 | |
3 | Auxiliary contact opening distance | mm | >155 | |
4 | Three phases on/off synchronism | ms | <3 | |
5 | Speed at break moment | m/s | >2.8 | |
6 | Speed at close moment | m/s | >3.8 | 2.8+0.4 |
7 | Earthing switch fracture distance | mm | 14.5±5 | |
8 | Primary loop resistance | μΩ | <120 | <300 |
9 | Max. operating torque | N.m | <160 | <180 |
Note:1. auxiliary opening distance value can be equal to the value after 24mm plus distance value of quiet arcing contact to end face of conductive drum nozzie
2. when measuring primary loop resistance of FKN122D combination apparatus, the fuse is instead by current conducting rod whose impedance can be ignored.
3.
3. Products photos:
4. Dimension and components descriptions:
What ar